  • 10KV或者35KV冷缩中间接头.jpg

10kV COLD SHRINK CABLE ACCESSORIES


Product Overview:

10KV cold shrink cable accessories are made of high quality liquid silicone rubber and complete cold shrink technology terminal and intermediate connector, convenient construction, safety, high quality. The product is widely used in power, petrochemical, metallurgy, railway, port and construction fields of medium voltage 6/10kv and 8.7/15kv grade power lines. KEYUACE can customize color terminal shrink tube.
Contact us
  • Product Features
  • Specifications
  • Technical data
  • Video

  •  

  • Product Code NAME For Cable mm2
    10kV  IN3 -3/1  10kV -3 cores - 25-50mm2
    10kV  IN3 -3/2   70-120mm2
    10kV  IN3 -3/3 indoor cold shrink terminal 150-240mm2
    10kV  IN3 -3/4   300-400mm2
    10kV  OUT3 -3/1  10kV-3 cores - outdoor cold shrink terminal 25-50mm2
    10kV OUT3 -3/2 70-120mm2
    10kV OUT3 -3/3 150-240mm2
    10kV OUT3 -3/4 300-400mm2
    10kV M/3 -3/1  10kV-3 cores - 25-50mm2
    10kV M3 -3/2   70-120mm2
    10kV M3 -1/3 cold shrink intermediate connection 150-240mm2
    10kV M3 -1/4   300-400mm2
    10kV IN1 -1/1  10kV -1 cores - 25-50mm2
    10kV IN1 -1/2   70-120mm2
    10kV IN1 -1/3 indoor cold shrink terminal 150-240mm2
    10kV IN1 -1/4   300-400mm2
    10kV OUT1 -1/1  10kV-1 cores - outdoor cold shrink terminal 25-50mm2
    10kV OUT1-1/2 70-120mm2
    10kV OUT1 -1/3 150-240mm2
    10kV OUT1 -1/4 300-400mm2
    10kV M1 -1/1  10kV-1cores - 25-50mm2
    10kV M1 -1/2   70-120mm2
    10kV M1 -1/3 cold shrink intermediate connection 150-240mm2
    10kV M1 -1/4   300-400mm2
  • Test project

    test method

    test results


    1min power frequency voltage (wet state)

    35kV NO breakdownNo flashover

    35kV,1min
     did not flashover and

    No breakdown in wet state

    Partial discharge test

    15kV discharge power is no more than 10PC

    A, B, C three phase at 15kV discharge for 3pc

    Load cycle test

    Conductor heating to 90-95 , and each cycle is 8 h, 5 h of heating and cooling 3 h, three time cycle

    Complete three load cycle tests according to the standard requirements

    Impulse voltage test

    95kV, positive and negative polarity 10 times no flashover, no breakdown

    10 times for positive and negative polarity of 95kV,

    The combined samples failed to flashover and breakdown

    AC voltage withstand test

    35kV NO breakdownNo flashover

    35kV4h
     did not flashover and

    No breakdown in wet state

    5min power frequency voltage test

    39kV NO breakdownNo flashover

    39kV5 min
     did not flashover and

    No breakdown in wet state